CM1-SERIES
INIT Group
In following pages, press
1 second to return theINIT
GROUP INDEX PAGE.
init: initialization (SET:7170)
Reading stable functions
Average Display update (Average):
Settable range:1~99 times;
Jittery Display caused by the noise or unstable signal.
User can set the times to average the readings, and to
get smoothly display. The meter’s sampling is
15cycle/sec;[ avg] set to be 3 to express the display
update with 5 times/sec
A b C d E F G H i J K L M
a b c d e f g h i j k l m
n o P q r S t U v W X y Z
n o p q r s t u v w x y z
1 2 3 4 5 6 7 8 9 0 / .
1 2 3 4 5 6 7 8 9 0 / .
Scaling Function
Setting Range: -1999~+9999 counts;
Users can set the parameters in the class is free to
set the input signal display low [lOsc] (Low
scale corresponding to the input lower limit)
and show high values [hIsc] (High scalelimit on
the corresponding input); can be set to negative slope.
Please refer to the following description
Moving Average update [mVavg]:
Settable range:1~99 times;
Jittery Display caused by the reasons as like as noise
or unstable signal. User can set the times to average
the readings, and get smoothly display.。
A v e ra g e s e t to be 3
Display Update Value =
(Sample 1 + Sample 2 + Sample 3)/3
Display Update Value =
(Sample 4 + Sample 5 + Sample 6)/3