Relay Functions
Energized / De-energized
Delay & Hysteresis
Fig.3
ON
Hysteresis
De-energized
delay
time
Hi Setting
Relay
Energized
[ry_.sp]
[ry_.hy]
[ry_.rd]
[ry_.fd]
Energized delay time
Relay energized delay and Relay de-energized delay
Settable range: 0.0(s)~9(m)59.9(s)
This function is primarily to avoid instrument disruption
or instability of input signals and relay misoperation
Relay energized delay [ ry_,rd] (Fig.4-): When
the value is reached when the conditions of the
relay, the relaywill delay action until
EX: Relay 1 setting
[ry!md]: hi[ry!rd]: )0%0[ry!sp]: 10)0
When (PV) over 10)1 (PV>[ry!sp])and keep over 5
secRelay output will be Action (ON)
Relay de-energized delay [ ry_,fd] (Fig.4-):
If the display value to leave therelay of the conditions
and set lasting more than this,the relay will reset
EX: Relay 1set
[ry!md]: hi[ry!fd]: )0@0[ry!sp]: 10)0
When (PV) less than 9(9 (PV<[ry!sp]) and keep
over 2 secRelay reset(OFF)
Energized / De-energized
Delay & Hysteresis
Fig.3
ON
Hysteresis
De-energized
delay
time
Hi Setting
Relay
Energized
[ry_.sp]
[ry_.hy]
[ry_.rd]
[ry_.fd]
Energized delay time
Analogue Output Functions
CM1 series offer the 2 relay outputsDifferent control
functions can be individually planned its related functions can
be set at the button panel . Details are as follows
Relay energized mode [ ry_.md]
selectionHi / Lo
Hi ( hi) (Fig.1-): Relay will be energized,
when PV > Set Point
Lo ( lo) (Fig.1-): Relay will be energized,
when PV < Set Point
Hi / Lo Relay Energized
Fig.1
hi
lo
[ry_.sp]
[ry_.sp]
[ry_.md]
Hi Setting
Hi Relay Energized
ON
Lo Setting
Lo Relay Energized
ON
Start delay band and Start delay time
The functions have Been designed for
1. To avoid starting current of inductive motor (6 times of
rated current) with alarm.
2. If the ry_.md relay energized mode had been set to
be lo(Lo) or lOhld(Lo & latch). As the meter is
power on and no input to display the "0" caused the
relay will be energized. User can set a band and
delay time to inhibit the energized of relay
Start of band of Relay energized [ rYsb] (Fig.2-)
Settable range from 0~9999 Digits
When displaying the value exceeds started after no
action, and then after startup delay time, the relay
will start the PV value is compared with the set value
output
Start band [ rYsd] (Fig.2-)
Settable range: 0.0 Sec~9(m)59.9(s)
Start Delay
Fig.2
Start Delay Time
Start Band
Hi Setting
Relay
Energized
ON
Inhibit
Inhibit
[ rYsb]
[ry_.sp]
[ rYsd]
Hysteresis [ ry_,hy] (Fig.3)
Settable range: 0~5000 Counts
As the display value is swing near by the set point to
cause the relay on and off frequently. The function is to
avoid the relay on and off frequently such as
compressor…….etc.,
User can set a band to prevent from the relay on and
off frequently
Please specify the output type either 0~10V or
4(0)~20mA in ordering code. The output low and high
can be programmable which it's related with various
display values. Reverse slope output is decided by
reversing point positions
Output range selection
Voltage output specified, Programming :
: V0-10(0~10V) / V0-5(0~5V) / V1-5(1~5V)
Currnet output specified Programming :
: A4-20(4~20mA) / A0-20(0~20mA) /A0-10(0~10mA)
Output signal corresponds to display value
Settable range: -19999~+29999/99999;
Low Output corresponds to Low display value
[ aOls]: Setting the Low Display value versus Low
output range (as like as 4mA in A4-20)
Analogue Output relative High Scale) [ aOls]: Setting
the High Display value versus High output range (as like
as 20mA in A4-20)