4.1 Timer Type Selection
A pop-up screen lets you scroll through the various timer types available.
Pulse - A water meter activated timer
Limit - Feed with bleed with a maximum run time or limit
for one bleed cycle.
Percent - A continuous cycle timer that sets a percentage
On time of a cycle.
Percent Post Bleed - For feed after bleed for a settable
percentage of the bleed time with a maximum run time.
28-Day - A biocide or event timer.
4.2 Timer Set Up
Each timer type selected will have its own unique Set Up
sub menu with additional selections specic to the type
of timer selected. The page displayed before entering
the Set Up menu of a timer provides an overall review
of the timers current settings.
4.3 Pulse Timer
ACCUMULATE - The number of gallons or liters from
water meter to count before activating timer.
RUN TIME - The amount of time for the timer to run
METER INPUT - Select water meter 1 or 2 for the
timer’s activation. Water meter 1 + 2 can be selected
only if the meters have the same contact value.
BLEED INTR - Allows the pulse timer to be interrupted
during conductivity bleed. While interrupted, you can
also dene the maximum number of timer run cycles
(1-9) to store for playback.
4.4 Percent Timer
% of CYCLE - The percent of the dened cycle time
that the timer is to be on.
CYCLE TIME - The amount of time in MM:SS that the
cycle is going to be on.
>SYSTEM 1 TIMER 1 SET UP<
>SET TIMER TYPE (PULSE)<
-> PULSE
USE UP/DOWN KEYS TO CHANGE
PRESS ENTER TO ACCEPT
SET UP TIMER TYPE
>SYSTEM 1 TIMER 1 SET UP<
TIMER TYPE: PULSE
GALLONS: 10
RUN TIME (MM:SS): 01:00
INPUT: WATER METER 1
SET UP TIMER TYPE
>SYSTEM 1 TIMER 1 CHANGE<
ACCUMULATE
RUN TIME
METER INPUT BLEED INTR
>SYSTEM 1 TIMER 1 CHANGE<
% OF CYCLE
CYCLE TIME