6-4-3 System Command Set
$aaAff
Name Set Integration Time
Description Sets an integration time to a specified ADAM-6000 module.
Syntax $aaAff(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal Modbus address
of the ADAM-6000 module you want to configure. (Always 01)
A is I/O module configuration command.
ff represents the integration time.
50 means 50ms (Operation Under 60 Hz power)
60 means 60ms (Operation Under 50 Hz power)
(cr) is the terminating character, carriage return (0Dh)
Response !aa(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or communication
error or if the specified address does not exist.
! delimiter character indicating a valid command was received.
? delimiter character indicating the command was invalid.
aa (range 00-FF) represents the 2-character hexadecimal address of an
ADAM-6000 module.
(cr) is the terminating character, carriage return (0Dh)
Example command: $01A50(cr)
response: !01(cr)
The ADAM-6000 module at address 01h is configured to an integration time
50ms (60Hz). The response indicates that the command has been received.
Note: An analog input module requires a maximum of 7 seconds to perform auto calibration
and ranging after it is reconfigured. During this time span, the module cannot be addressed to
perform any other actions.