Loading...
$aaF
Name Read Firmware Version
Description Returns the firmware version code from a specified ADAM-6000 module.
Syntax $aaF(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal Modbus address
of the ADAM-6000 module you want to interrogate. (Always 01)
F is the Firmware Version command.
(cr) is the terminating character, carriage return (0Dh).
Response !aa(version)(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error, communication
error or if the specified address does not exist.
! delimiter character indicating a valid command was received.
? delimiter character indicating the command was invalid.
aa (range 00-FF) represents the 2-character hexadecimal address of an
ADAM-6000 module.
(version) represents the firmware version of the ADAM-6000 module.
(cr) is the terminating character, carriage return (0Dh).
Example command: $01F(cr)
response: !01A1.01(cr)
The command requests the system at address 01h to send its firmware version.
The system responds with firmware version A1.01.