True Online 1-3k UPS User Manual
7
2. Electrical Performance
Input
Model Voltage Frequency Power Factor
1-3KVA Single-phase 40-70Hz >0.98(Full load)
3. Operating Environment
Temperature Humidity Altitude Storage temperature
0°C-40°C <95% <1000m -20°C-70°C
NOTICEIf the UPS is installed or used in a place where the altitude is above than 1000m,
the output power must be derated in use, please refer to the following:
Altitude (M)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Derating Power
100%
95%
91%
86%
82%
78%
74%
70%
67%
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion Overload capacity Crest ratio
±1%
0.8 lag
or
0.9 lag
±0.5% of
normal
THD<3%@Fu
ll Linear Load
THD<6%@Fu
ll nonlinear
load
105%~130% load:
transfers to Bypass mod
e
after 1 minutes
130%~150% load:
transfers to Bypass mode
after 0.5 minute
3:1
maximum