5
D)ConfigurationofRelayOutputs
E)PersonalSafety
F)DoorForced-Open-Alarm&VisitorAnnouncing
G)AllowableDoor-Left-OpenTimeforDoor-Open-Too-LongAlarm
--InstallerProgramming
--InstallerProgramming
--InstallerProgramming
--InstallerProgramming
40#
41#
42#
50#
51#
52#
60#
61#
62#
70#
71#
72#
76#
80#
81#
82#
83#
9#
9#
1to999Output1inMomentaryModefrom1to999seconds
Output1inStart/StopModewithoutacceleratedcode
Output1inStart/StopModewithacceleratedcode
1to999Output2inMomentaryModefrom1to999seconds
Output2inStart/StopModewithoutacceleratedcode
Output2inStart/StopModewithacceleratedcode
1to999Output3inMomentaryModefrom1to999seconds
Output3inStart/StopModewithoutacceleratedcode
Output3inStart/StopModewithacceleratedcode
After10successivefalsecodes,thekeypadlocksduring
30seconds
After10successivefalsecodes,theDuressOutput
swit chestoground
5to10Selectableof5to10successivefalsecodes,thekeypad
locksduring15minutes.Thekeypadcanberesetto
releaselockingwiththeMasterCodeatanytimeduring
thelockingperiod
00Disappearanceofalltheabovesecurities
DoorForced-Open-AlarmdetectionisDisabled
DoorForced-Open-AlarmdetectionisEnabled
VisitorannouncingchimeisgiveniftheUserCodeinGroup1isnotkeyedinfirst
whenthedoorisopened.
Visitorannouncingchimeisalwaysgivenwhenthedoorisopened
0ThetimerisDisabled.Allowsthedooraninfinitetimetoopenfor
1to999Allowabletim efrom1to999secondsfordooropenbeforethe
Door-Open-Too-Longalarmistriggered
AccessKeysCodeDuration
AccessKeysNumberofFalseEntryValidationComments
AccessKeysValidationComments
AccessKeysCodeDurationValidationComments
ValidationComments
6
H)ExitProgrammingMode
TheDefaultValues
*
Keypadexitsprogrammingmodeandreturnstonormaloperation
SingleUserModeifitisyourselection.
Output2is1SecondMomentaryMode
601---Output3is1SecondMomentaryMode
70-----After10SuccessiveFalseCode,TheKeypadLocksDuring30Seconds
80-----DoorForce-Open-AlarmDetectionisDisabled
90-----TheDoorOpen-Too-longTimerisDisabled
ThemodeofforeachoutputonlyallowUserCodeforeachoutput,anditisfixedto4
digits.ThismodeispreparedforthosepeopleDONOTliketoPresstheforcodeentrytoactivatetheoutput.
Theyonlypressthe4digitsUserCode,then,the specificoutputisactivated.Eachoutputhasitsowncode.
SINGLEUSERORMULTI-USERSSELECTION
Thekeypadconsiststwosetsofapplicationsoftwareforowner'sselectioninusercodeprogramming.Oneis
"SingleUserCodeforEachOutput"andtheotheris"Multi-UserCodesforEachOutput".
ThekeypadhasbeensetwithaMasterCodeof"0000"andMultiUserModewiththefollowing"DefaultValues"at
thefactory.YoudonotrequiretomakeanyoperationmodechangeifyourselectionisMulti-UserMode.However,
Youhavetorefreshthesystemto
0000
401---Output1is1SecondMomentaryMode
501---
TheSingleUserCode
SingleUserCodeONE
!
!
!
ValidationComments
#
#
TheMulti-UserCodes
CodeEntryLimitationforMulti-UserCodes
Themodeofispreparedforsettingupagroupofusercodesforeachoutput.TheUserCodescanbe
4to8digits.Toactivatethedesiredoutput,theuserhastopressthekeytoconfirmofcodeentryinthe
operationoftheMulti-UserCode.ThefollowingarethenumberofUserCodesavailableineachgroup:
UserCodesinGroup1forOutput1---100Users
UserCodesinGroup2forOutput2---10Users
UserCodesinGroup3forOutput3---10Users
AsthesystemcomeswithfunctionandtheDURESSCODEissettingupbythesystemautomaticallywith
thefirstdigitoftheUserCode"+2".TopreventtheotherUserCod esfallintotheDuressCode,ortheDuress
CodesfallintootherUserCodes,thefirstdigitofa""Usercode"+2"or"-2"isnotallowedforthelater
UserCodeentryinprogramming.Thesystemwillrefusethosecodeentries.
AnUserCode56789issavedinthesystem,then36789and76789arenotallowedasotherUser
Codes.
Multi-Users
DURESS
Saved
Forexample:
TheFactorySetMasterCode