Innovation Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0078_0L AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 47 of 206
GF-128 Phone: 800-526-0288 PRI: 11/25/2014
Menu Item Display
Available Choices or Limits
Default
WHM Items – the following item appear only if WHM is enabled
20 FDback Start Pos 0% 100% 30%
21 Fdback End Pos 0% 100% 60%
22 Max Feedback 0% 100% 30%
23 Fdback Value 0% 100% Read Only Value
24 Temp Gov Enable or Disable Enable
25 GOV Limit-5 0 100 30
26 GOV Limit-7 0 100 20
27 GOV Limit-10 0 100 15
28 GOV Limit-12 0 100 10
29 GOV Limit-15 0 100 5
30 PID Output 0% 100% Read Only Value
31 P Output 0% 100% Read Only Value
32 I Output 0% 100% Read Only Value
33 D Output 0% 100% Read Only Value
34 Reset Defaults Yes No No
3.8 CALIBRATION MENU
The Calibration Menu is used by Factory Trained Service personnel to adjust or reset the
parameters listed below.
A full description of each item appears in Table A-5 of Appendix A – Innovation Menu Item
Descriptions.
Table 3-6: Calibration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum Maximum
1
Stepper Fbk
Cal 0%
Cal 100%
Cal 0%
2 Purge Timer 5 sec. 60 sec Depends on unit type/size
3 Post Purge Timer 0 sec. 60 sec. 0 sec.
4 IGN Position 5% 60% Depends on unit type/size
5 FFWD Temp Disply Enabled or Disabled
6 Outlet Tmp Dsply Enabled or Disabled
7 Inlet Tmp Dsply Enabled or Disabled
8 Valv Pos Out Dsp Enabled or Disabled