APPENDIX A
A-2
WATER HEATER MENU ITEM DESCRIPTIONS - Continued
MENU LEVEL & OPTION DESCRIPTION
SETUP MENU
Password Allows password to be entered.
Once the valid password (159) is entered, options
in the Setup, Configuration and Tuning Menus
can be modified.
Language English Only
Time Displays time from 12:00am to 11:59pm.
Date Displays dates from 01/01/00 to 12/31/99
Unit of Temp Permits selection of temperature displays in
degrees Fahrenheit (°F) or degrees Celsius (°C).
Default is °F.
Comm Address For RS-485 communications (0 to 127). Default
address is 0. RS-232 should have its own
(programmable) password.
Baud Rate Allows communications Baud Rate to be set
(2400 to 19.2K). Default is 9600.
Software Version Identifies the current software version of the
control box (Ver 0.00 to Ver 9.99).