SPL User Manual Page 20 of 24 0412-6180864-rev.00
Room air temperature probe error
(ambient air intake)
Check wiring or replace
component
Disable delivery limit
function
Delivery temperature probe error
Check wiring or replace
component
Disable economizer
(freecooling,
freeheating)
External temperature probe error
Check wiring or replace
component
Disables anti-freeze
function
Water coil anti-freeze temperature
probe error
Check wiring or replace
component
>Delivery fan differential pressure
switch probe error
Check wiring or replace
component
Disables humidifier
delivery limit
Delivery humidity probe error
Check wiring or replace
component
Disables enthalpy
economizer
(freecooling,
freeheating)
External humidity probe error
Check wiring or replace
component
Disables enthalpy
economizer
(freecooling,
freeheating)
Dehumidification,
humidification
Ambient humidity probe error
(ambient air intake)
Check wiring or replace
component
Disables air quality
function
Check wiring or replace
component
Circuit maximum probe error (high
pressure transducer)
Check wiring or replace
component
Circuit minimum probe error (low
pressure transducer)
Check wiring or replace
component
N.B.: “#” indicates the number of the circuit, the compressor, the thermal switch, etc..