17. TROUBLE SHOOTING
IRREGULARITY CAUSE SOLUTION
The unit does not start
No electrical voltage
Check for voltage
Check the safety systems upstream of the appliance
Master switch on OFF

Control panel on OFF
Main switch on OFF
Compressor thermomagnetic switch on OFF
Set to ON
The flow switch is not connected on the terminal
board therefore the circuit is open
Install and wire the flow switch
NB. DO NOT bridge the contacts on the terminal

of insufficient water and the exchanger would be to

Power supply voltage too low Check power supply line
Coil of the compressor remote control switch is
broken
Electronic circuit board faulty
Peak condenser faulty
Compressor faulty
Replace the component
Poor yield
No refrigerant
Dirty coils
Water filter clogged
Appliance dimensioning
Operating outside the operating limits
Check the load and any leaks
Clean the coils
Clean the filter
Check performance
Check the operating limits using the graphics
Compressor noisy
Liquid return to the compressor
Inadequate fixing
Check
Inverted phase Invert a phase
Noises and vibrations
Contact between metallic bodies Check
Weak support Strengthen
Loose screws Tighten the screws
The compressor stops due to the intervention of the
protections
Excessive flow pressure
Low intake pressure
Low power supply voltage
Electrical connections tightened badly
Operation outside operating limits
Check the operating limits using the graphics
Pressure switch malfunctioning Replace the component
Circuit breaker protection intervention
Check the power supply voltage and calibrations
Check the electrical isolation of the windings
Flow switch intervention Check water flow rate
Compressor high discharge pressure
High external air temperature
High utility inlet water temperature
Check the operating limits using the graphics
Insufficient air flow
Insufficient water flow
Control:
1. operation of the fans
2. Cleanliness of the coil
3. 
4. Cleanliness of the filter
Anomalous operation adjusting the fans Check or replace if broken
Air in the hydraulic system Vent the circuit
Too much refrigerant gas charged Restore the correct charge
Low discharge pressure
Low outside air temperature
Low water inlet temperature
Check the operating limits using the graphics, as
above
Moisture in the refrigerant circuit Empty and restore the gas charge
Air in the hydraulic system Bleed the circuit
Insufficient gas load Restore the correct load
High intake pressure
High external air temperature
High utility inlet water temperature
Thermostatic expansion valve too open or damaged
Check the operating limits using the graphics
Adjust or replace if damaged
Low intake pressure
Utilities low inlet water temperature
Low outside air temperature
Thermostatic expansion valve damaged or blocked
Check the operating limits using the graphics
Adjust or replace if damaged
Insufficient water flow
Insufficient air flow
Control:
1. operation of the fans
2. Cleanliness of the coil
3. 
4. Filter cleanliness