3918.01._5280107_02
NRL 0280-0750 °-L / A-E
EN
L1 L2 L3 N
TERRA (PE)
FASE NEUTRO
Alimentazione:
0280 400V/3N/50Hz 2 6 49,41 158 3+N 1
16
16 4 1,5 16 63
0300 400V/3N/50Hz 2 6 56,41 187 3+N 1
16
16 4 1,5 16 63
0330 400V/3N/50Hz 2 8 64,41 193 3+N 1
25
16 4 1,5 16 80
0350 400V/3N/50Hz 2 8 66,41 203 3+N 1
25
16 4 1,5 16 80
0500 400V/3N/50Hz 2 2 80,53 219 3+N 1
50
25 4 1,5 25 125
0550 400V/3N/50Hz 3 2 85,53 225 3+N 1
50
25 4 1,5 25 125
0600 400V/3N/50Hz 4 2 105,86 238 3+N 1
5
25 4 1,5 25 125
0650 400V/3N/50Hz 4 2 117,86 249 3+N 1
70
35 4 1,5 35 160
0700 400V/3N/50Hz 4 3 127,86 267 3+N 1
70
35 4 1,5 35 160
0750 400V/3N/50Hz 4 3 144 320 3+N 1
95
35 4 1,5 50 200
NRL A - E
NRL SIZE
Power supply





F.L.A.
L.R.A.
SEZ. A SEC. B  
 
Phases

Cables
for single

Cable
cross-
section

Neutral
cross-
section


cables

[mm
2
[mm
2


 Initial starting current
 Maximum input current
 Power supply
 Controls and safety device connection
: Earth wire to connect to unit
 Master switch