DATI ELETTRICI 27 H 37 H 47 H 57 H 77 H 107 H 127 H
Corrente assorbita • Current absorption
[A] (1) 8,8 13,3 16,2 ----
[A] (2) - 6,1 7,0 7,4 9,5 15,0 18,0
Corrente assorbita • Current absorption
[A] (1) 10,6 17,8 21 ----
[A] (2) - 7,5 8 9,0 13,9 18,3 21,8
Corrente di spunto • Peak current
[A] (1) 47,0 95,0 116,0 ----
[A] (2) - 43,5 52,0 66,0 102,0 130,0 135,0
Corrente max. • Max.current
[A] (1) 11,0 18,0 22,7 ----
[A] (2) - 8,0 8,9 13,0 14,0 20,0 32,0
ATTACCHI IDRAULICI E DIMENSIONI • WATER CONNC. AND DIMEN. 27 H 37 H 47 H 57 H 77 H 107 H 127 H
Attacchi idraulici • Water connec. Ø Gas 1”/F 1”/F 1”/F 1”/M 1”/M 1”/M 1”/M
DATI DIMENSIONALI • DIMENSIONS 27H 37 H 47 H 57 H 77 H 107 H 127 H
Altezza • Height [mm] 1140 1140 1140 850 850 950 950
Dimensioni - Dimensions Larghezza • Width [mm] 450 450 450 450 450 450 450
Profondità • Depth [mm] 450 450 450 650 650 700 700
Peso a vuoto • Net weight [kg] 101 112 118 102 124 160 189
Le prestazioni sono riferite alle seguenti condizioni:
Temp. acqua prodotta = 7 °C
Temp. ingresso condensatore = 30 °C; Temp. uscita condensatore = 35 °C;
Temp. acqua prodotta =50 °C
Temp. ingresso evaporatore = 10 °C; Temp. uscita condensatore = 5 °C
Pressione misurata in camera semiriverberante di 85 m
3
e con tempo di riverberazione Tr = 0,5s.
La potenza elettrica comprende l’assorbimento della pompa di circolazione alla massima velocità.
Performances refer to following conditions:
Temp.processed water = 7 °C
Temp. of condenser inlet water = 30 °C; Codenser water outlet temp. = 35 °C
Temp.processed water = 50 °C
Temp. of condenser inlet water = 10 °C; Codenser water outlet temp. = 5 °C
Sound pressure measures in a 85 85 m
3
semi-reverberating room and with a reverberating time Tr = 0,5 s.
Electrical power includes circulation pump absorption at maximun speed.
POMP
POMP
A DI C
A DI C
ALORE •
ALORE •
HEA
HEA
T PUMPS R407C
T PUMPS R407C
(1) Tensione di alimentazione • Power supply = 3~230V-50Hz.
(2) Tensione di alimentazione • Power supply = 3~400V-50Hz.
NRW Cod. 6557920_02 17

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC NRW 127 H and is the answer not in the manual?

AERMEC NRW 127 H Specifications

General IconGeneral
BrandAERMEC
ModelNRW 127 H
CategoryChiller
LanguageEnglish

Related product manuals