AERMEC NXW - INPUTS;OUTPUTS Menu - Component Status; Compressor Flow Switch Inputs; Compressor 2 Circuit Breaker & Phases; High;Low Pressure Switch Status (Circuit 2)

AERMEC NXW
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
48
INPUTS/OUTPUTS menu - Compressor magnet circuit breaker flow switch digital inputs
Visualisation on unit display Index Display/Parameter
A Inputs/Outputs: Indicates the state of the different entries/exits.
B Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C 05: indicates the status of the flow switch positioned on the
evaporator, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = minimum water flow rate threshold exceeded at the
evaporator (Flow switch alarm);
D
06: indicates the status of the compressor magnet circuit breaker
indicated, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = the compressor load has exceeded the maximum
threshold (Compressor magnet circuit breaker alarm);
INPUTS/OUTPUTS menu - Compressor 2 magnet circuit breaker digital inputs and compressor phases
Visualisation on unit display Index Display/Parameter
A Inputs/Outputs: Indicates the state of the different entries/exits.
B Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C
07: indicates the status of the compressor magnet circuit breaker
indicated, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = the compressor load has exceeded the maximum
threshold (Compressor magnet circuit breaker alarm);
D 08: indicates the status of the phase control on the compres-
sors, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = incorrect phases detected on the compressor indi-
cated (Serious alarm);
B
Input/Output
Master digital input
A
C
05= Evap.water flow:
Close
06= Ovrl.cmp.1 circ.1:
Close
D
B
Input/Output
Master digital input
A
C
07= Ovrl.cmp.2 circ.1
Close
08= Serious alarm:
Close
D
INPUTS/OUTPUTS menu - HIGH/LOW pressure pressure switch status digital inputs (circuit 2)
Visualisation on unit display Index Display/Parameter
A Inputs/Outputs: Indicates the state of the different entries/
exits.
B Master: indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C 01: indicates the status of the high pressure switch, mounted
on the cooling circuit indicated. The status of this component
can be one of the following:
• Closed = normal working state;
• Open = maximum pressure threshold exceeded
(HIGH PRESSURE alarm);
D 02: indicates the status of the low pressure switch, mounted
on the cooling circuit indicated. The status of this component
can be one of the following:
• Closed = normal working state;
• Open = minimum pressure threshold exceeded
(LOW PRESSURE alarm);
B
Input/Output
Master digital input
A
C
09= High press.circ.2:
Close
10= Low press.circ.2:
Close
D