EasyManua.ls Logo

AERMEC VED 641 - POSSIBLE CONFIGURATIONS WITH THERMOSTATS; Accessory Notes and Fan Coil Configurations; VED Combined with VMF-System Controls; VED Combined with Control Panels and Thermostats

AERMEC VED 641
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
49
IVEDPY 1110 - 4879010_01
POSSIBLE CONFIGURATIONS OF THE VED FAN COILS WITH THE AVAILABLE THERMOSTATS
Single unit Fan coil network
VED FAN COILS
VED
4X - 5X
VED
6X - 7X
VED
4X - 5X
VED
6X - 7X
VED
4X - 5X
VED
6X - 7X
VED
4X - 5X
VED
6X - 7X
VED
4X - 5X
VED
6X - 7X
VED
4X - 5X
VED
6X - 7X
ACCESSORY NOTES
FAN COIL CONFIGURATION
Without valves
Two pipe circuit
with valve
Four pipe circuit
with valve
VED network
Without valves
VED network
Two pipe circuit with
valve
VED network
Four pipe circuit with
valve
VED combined with VMF-System series control devices
VMF-SIT3 (4A) Thermostat interface Mandatory accessory Mandatory accessory between the VED fan coil and the VMF-E0 or VMF-E1 thermostats
VMF-E0 (0.7A)
VMF-E1 (0.7A)
VMF-System thermostats
Obligatory accessories
Permitted combinations
(mandatory combination with VMF-SIT3)
Permitted combinations (mandatory combination with VMF-SIT3)
Possible combinations:
VMF-EI (Master) + VMF-E1 (Slave)
VMF-EI (Master) + VMF-E0 (Slave)
VMF-E0 (Master) + VMF-E0 (Slave)
VMF-E4
VMF-System control panels
Single unit
To be combined with thermostats VMF-E0 and VMF-E1
Fan coil network
To be combined with thermostats VMF-E0 (Master) and VMF-E1 (Master)
VMF - E5
Control panel for VMF- E1
stand alone or for a WMF
network in which the first
is a VMF-E1.
Single unit
To be combined with a VMF-E1 thermostat
Fan coil network
To be combined with VMF-E1 (Master) thermostats
VED combined with control panels with thermostat
PXAE (1.1A)
Command panels with
thermostat
Combinations allowed for installation on a single unit
(mandatory combination with SIT3)
Combinations permitted for networked VED fan coils installation
(mandatory combination with SIT3 + SIT5)
WMT05 (3A)
Command panels with
thermostat
Permitted Not permitted Not permitted Permitted with SIT3 Not permitted Not permitted
WMT06 (3A)
Command panels with
thermostat
Permitted Permitted Permitted Permitted with SIT3 Permitted with SIT3 Permitted with SIT3
WMT10 (1.4A)
Command panels with
thermostat
Permitted
Permitted
with SIT3
Permitted
Permitted
with SIT3
Permitted
Permitted
with SIT3
Permitted with SIT3 Permitted with SIT3 Permitted with SIT3
SIT3 (4A) Control panel interface
Mandatory accessory in a VED network (max 3), one for each unit controlled by control panels with thermostat.
Interface mandatory between the VED fan coils and the WMT10 control panels (as indicated in the table)
SIT5 (4A)
PXAE Control panel net-
work interface
Not permitted
Interface mandatory between the VED fan coils and the PXAE control panels
SW3 Water temperature probe PXAE control panel dedicated accessory