2. 0
P26
Heating proportional
band (°C)
0. 9 .. 8. 0
2. 0
P27
Cooling proportional
band (°C)
0. 9 .. 8. 0
0
P28
Heating integrative
time (minutes)
0 .. 30
0
P29
Cooling integrative
time (minutes)
0 .. 30
33
P30
Fan MIN
speed (FI1)
1 .. 100
66
P31
Fan MED
speed (FI2)
1 ..100
100
P32
Fan MAX
speed (FI3)
1 ..100
0
P33
Fan-coil signal
lower limit
0. 0 ..10. 0
10. 0
P34
Fan-coil signal
upper limit
0. 0 ..10. 0
0
P35
Dirty filter warning
time (x 100 hours)
0 .. 50
END
0. 0
P12
Room temperature
correction (offset) (°C)
-5. 0 .. 5. 0
10
. 0
P13
Heating set-point knob
lower limit (°C)
5. 0 .. 35. 0
30
. 0
P14
Heating set-point knob
upper limit (°C)
5. 0 .. 35. 0
10. 0
P15
Cooling set-point knob
lower limit (°C)
5. 0 .. 35. 0
30
. 0
P16
Cooling set-point knob
upper limit (°C)
5. 0 .. 35. 0
0. 0
P17
Anti-freeze threshold
temperature (°C)
0. 0 .. 15. 0
0. 0
P18
Economy
reduction (°C)
0. 0 ..10. 0
0
. 2
P19
Ambient temperature
hysteresis (°C)
0. 2 ..1. 0
3
. 0
P20
Neutral zone
width (°C)
1. 0 ..11. 0
0
P21
Fan delay at
turn-on (seconds)
0 .. 600
0
P22
Fan delay at
turn-off (seconds)
0 .. 600
17
P23
Changeover
lower threshold (°C)
0 .. 24
30
P24
Changeover
upper threshold (°C)
26 .. 48
40
P25
Cut-off thermostat
threshold temperature (°C)
0 .. 99