EasyManua.ls Logo

AERMEC WMT20 - Summary of Parameters Involved in the ‘Installer’ Configuration

AERMEC WMT20
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
Table 1: Installer configuration (Summary of the parameters involved in the ‘installer’ configuration).
ENGLISHESPAÑOL DEUTSCH ITALIANOFRANÇAIS
COn
0
P01
System type
0
2-pipes system
1
4-pipes system
0
P02
Heating/cooling
selection
0
Manual
1
Automatic
2
Remote
3
Reversed
remote
3
P03
Heating
regulation
1
Valves only
2
Fan only
3
Valves and fan
3
P04
Cooling
regulation
1
Valves only
2
Fan only
3
Valves and fan
0
P05
Heating output
type
0
NC
ON/OFF valve
1
NA
ON/OFF valve
0
P06
Cooling output type
0
NC
ON/OFF valve
1
NA
ON/OFF valve
0
P07
Fan output
type
0
Direct action
1
Reversed action
0
P08
Supply water
sensor input
0
Do not show
temperature
1
Show
temperature
2
Bi-metallic
contact
3
Window
contact
4
Reversed
window contact
0
P09
De-stratification
0
Never
1
Cooling only
2
Heating only
3
Always
1
P10
On/Off state
at power up
1
Last
2
Always ON
3
Always OFF
0
P11
Room
temperature sensor
0
Internal
1
External
DEFAULT