EasyManuals Logo

AERMEC WWB 0900 User Manual

AERMEC WWB 0900
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
25
MAINTENANCE  LIST OF THE RECOMMENDED PERIODIC INTERVENTIONS
MAINTENANCE - LIST OF THE RECOMMENDED PERIODIC INTERVENTIONS
1 we do not recommend swabbing as it can ruin the inner lining of the pipes, we recommend using appropriate chemicals
RECOMMENDED PERIODIC MAINTENANCE INTERVENTIONS
DESCRIPTION
FREQUENCY
3/4
months
6
months
12
months
24
months
functioning hours
GENERAL INTERVENTIONS
Check of any refrigerant leaks (this must be done respecting the deadlines recommend-
ed by the current European regulations)
Check of the unit power supply voltage
Check of the compressors' power supply voltage
Check of the fan power supply voltage if present
Check of the solenoid valves
Functioning and calibration check of the pressure switches, if and where present
Replacement of the safety valve
Check and reading of the pressure/temperature probes
Check and possible replacement of the dehydrating  lters
Check of compressors contactors
Check of fans contactors, where present
Exchanger coils cleaning (preferably from the inside to the outside)
Check and cleaning of shell and tube heat exchangers if necessary where present (1)
Check of electric resistances of the heat exchangers
Check for rust and corrosion in components, paying particular attention to under pres-
sure containers. In this case replace them of intervene with speci c products
General cleaning of the unit
Bleed the hydraulic circuit and the heat exchangers, the simultaneous presence of air
and water reduces yield and can bene t the arising of rust
INTERVENTIONS TO COOLING CIRCUIT Functioning at full load
Overheating temperature measurement
Subcooling temperature measurement
Exhaust gas temperature measurement
Fans absorption measurement
Compressors absorption measurement
COMPRESSOR CHECKS
Check oil level
Check oil acidity
Check the proper functioning of the casing resistance
Check oil level sensor, if any
CHECKS ON HYDRAULIC CIRCUIT
Pumps absorption measurement
Check the pump rotor gasket
Check the  exible joints
Check the seal of the shell and tube heat exchanger heads, where present
Check the proper functioning and calibration of the  ow switch, where present
Check the proper functioning of the di erential pressure switch, where present
Check the concentration of glycol solution, if provided
3
months
*
Cleaning the water  lter
The frequency of the operations described herein is a guideline one and they may vary depending on how the unit is used and the type of system
where it is installed. However, if the unit is installed in harsh environments, we recommend reducing the time of intervention
* To replace the glycol, refer to the documentation provided by the supplier.