EPIC 2DEPIC 2D
ALARM
CODE
ALARM
DESCRIPTION
PUMP
STOP
RELAY
ON
LED
SIGNAL
AL 1
MIN VOLTAGE
YES YES
AL 2
MAX VOLTAGE
YES YES
AL 3
LOW FREQUENCY
NO YES
AL 4
HIGH FREQUENCY
NO YES
AL 5
DRY RUNNING P1/P2
YES YES
AL 6
MAX AMPERAGE P1/P2
YES YES
AL 7
MAX STAR PER HOUR
NO YES
AL 7
TIME ON MAX +
MAX START PER HOUR
YES YES
AL 8
WATER IN OIL CHAMBER
P1/P2
NO YES
AL 9
KLIXON P1/P2
YES YES
AL 10
MIN LEVEL
YES YES
AL 11
MAX LEVEL
NO YES
General useGeneral use
4.2 ALARMS
The control panel signals a series of alarms that
may occur during operation. Some of these stop
the pumps, while others are only displayed.
All alarms are displayed on the panel (red LED
flashing), while the display shows the code/alarms
occurred until the cancellation by the operator.
The alarm “AL 11” starts all the available pumps.
ALARM WITH STOP PUMP
Following the detection of an alarm and the consequent blocking of the pump, the
control panel provides the following operations:
• Try the first restart after 5 min.
• In case of a negative result, make another attempt after 30 min. and 3 other
attempts with intervals of 60 min.
• After 5 attempts if the alarm persists, the control panel permanently blocks the
pump and the alarm remains active until the user intervenes.
DELETE ALARM
0
P1
0
P2
To delete the alarms, enter the “0” button for pump 1 once and the
“0” button for pump 2.
IMPORTANT!
If after having canceled the alarm, the same occurs again, an intervention on the
cause is necessary.