- 16 -
Parameter settings
User parameters (can be adjusted by users.)
1. On main interface screen, press for 5 seconds to enter into user parameter query
interface, press and buttons to check each parameter. Please refer to the
relevant parameter list below.
2. On user parameter query interface, press to enter into parameter setting interface,
press and buttons to modify parameter value, press again to save
value and go back to user parameter query interface.
3. Press at any time to confirm settings and go back to main operation interface.
Set how much water temp difference to restart heat
pump automatically again. i.e. Heat pump will stop
heating once water temperature reaching to set water
temperature 28
℃
in heat mode (for instance). If this
parameter is set to 2
℃
, heat pump won't restart until
water temperature drops to 26
℃
.
Set target water temperature when in Heat mode.
Set target water temperature when in Cool mode.
Set upper limit of compressor current. There will
be an
alert if value exceeds this limit. ‘0’ for no
detection. (set for
3- phase units only).
Set buzzer ON or OFF when heat pump goes to an error
mode.
0 / 1
0: When target water temp reached and the heat pump
will shut down, water pump still keeps running.
1: When target water temp reached and the heat pump
will shut down, and water pump will stop running.
-
-