Three-phase Inverter Zero-Injection FAQ
Note:
Due to the fluctuation on the grid side, the data transition delay will
occur between smart meter and inverter. And the values displayed
on the smart meter and inverter will be different.
d. If wiring order of the three phases on the smart meter is incorrect, the current
values of the three phases displayed on the smart meter will be different, the two
phases that are incorrectly wiring will be smaller than the third phase.
-1.053
PGrid: -1053W
EtoGDay: 8505W
Inverter Grid Power
Three-phase Smart Meter
A
8.13
1[
A
12.27
1A
Current value of the two phases
incorrectly wiring:
Current value of the third phase: