GC, GE Open Flue Models
Maximum Heat Input: 4.4kw (15,000 (Btu/h)
GC, GE Direct Vent Models
The appliance and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.5kPa). The appliance must be
isolated from the gas supply piping system by closing the
individual manual shut-off valve during any pressure
testing of the gas supply piping system at test pressures
equal to or less than 1/2 psig (3.5kPa).
The model and serial numbers for this appliance are
found on the name plate. These numbers must be used
when requesting advice from your Aga Distributor. The
name plate is located on the inside face of the outer
burner door. The maximum gas inlet pressure at the
appliance must not exceed 12 inches w.g. (2.98kPa) for
Natural Gas and 14 inches w.g. (3.48kPa) for L.P. Gas.
The minimum gas inlet pressure at the appliance must be
4 inches w.g. (1kPa) Natural Gas and 10 inched w.g.
(2.248kPa) L.P. Gas to enable the correct manifold
pressure to be obtained.
4
LOCATION OF NAME PLATE