16
The SLIMLINE PERFORMER Ceilin
g
Cassette
Ductless Mini-S
p
lit
Technical Manual : AIR 8-105.5
Ceiling Cassette
Table 16.1 – Technical Data – Chilled Water Units
Units
CCW2/8 CCW2/12 CCW 18 CCW 20 CCW 33 CCW 36
Nominal Cooling Capacity (1)
BTU/h 6,601 11,091 17,592 19,087 29,722 35,258
Construction
Material: Fascia High Impact Polystyrene
Material: Chassis Galvanized Steel
Color: Fascia Pearl Grey
Fire rating UL94 VO
Chilled Water Coil
Type Finned Tube
Quantity 1 1 1 1 1 1
Face Area Ft² 1.8 1.8 2.8 2.8 5.2 5.2
Nominal Airflow High cfm 350 350 630 700 970 1160
Med cfm 300 300 530 630 890 970
Low cfm 260 260 500 530 785 890
Discharge 4-way 4-way 4-way 4-way 4-way 4-way
Unit water Volume gal 0.29 0.29 0.45 0.45 0.79 0.79
Fan
Type Centrifugal
Quantity 1 1 1 1 2 2
Diameter in 12 12 15 15 14 14
Horsepower (per fan) HP 1/8 1/8 1/8 1/8 1/8 1/8
Weights
Weight - Chassis lb 40 40 64 64 97 97
Weight - Fascia lb 5 5 18 18 21 21
Connections
Chilled Water Inlet in 5/8 5/8 7/8 7/8 7/8 7/8
Chilled Water Outlet in 5/8 5/8 7/8 7/8 7/8 7/8
Condensate (ID) in 3/8 3/8 3/8 3/8 3/8 3/8
Filtration
Type Wire Framed Periframe
Quantity 1 1 2 2 3 3
Arrestance 80% 80% 80% 80% 80% 80%
Condensate Pump
Maximum Head in 30 30 30 30 30 30
Nominal Flowrate gpm 0.1 0.1 0.1 0.1 0.1 0.1
Options
Electric Heating Capacity kW 1.5 1.5 3.0 3.0 5.0 5.0
HW Heating Capacity (2) BTU/h 13,799 N/A 29,258 30,946 46,455 51,600
HW Coil Connection (OD) in 5/8 N/A 5/8 5/8 5/8 5/8
Max Branch Duct Connections (qty) 2 2 2 2 2 2
Branch Duct Diameter in 5 5 5 5 6 6
Ducted Air Volume (3) cfm 80 80 100 125 200 220
Fresh Air Connections (qty) 1-2 1-2 1-3 1-3 1-3 1-3
Fresh Air Duct Diameter in 3 3 3 3 3 3
Fresh Air Volume (4) cfm 40 40 60 65 90 95
(1) Nominal cooling capacity based on 80/67°F DB/WB and water temperature of 45ºF inlet / 55ºF outlet.
(2) Nominal heating capacity based on 70/60°F DB/WB and water temperature of 180ºF inlet / 160ºF outlet.
(3) Maximum air volume available through one branch duct 6' long, with Cassette fan(s) at high speed and corresponding fascia
aperture closed.
(4) Maximum fresh air through all knockouts connected to one 10' long duct with fan at high speed.