44
TC4-2N6F.rev.07
CAUSE
SOLUTION
PROBLEM
There is no
display.
The circuit breaker
at the service panel
is off or tripped.
Reset the circuit breaker.
The wiring is
incorrect.
Correct the wiring.
The voltage selector
switch is in the
wrong position.
Set the switch to the correct
position.
The display board
interconnect cable
is not properly
plugged into the
power supply board.
Be sure the cable is firmly
plugged in.
The display
shows "P" when
the parameter
selection knob
is set to OUT-
SIDE SET-
TINGS.
The outside probe
is connected
improperly.
Correct the outside probe
connection.
The outside probe is
defective.
Refer to "Defective Probes"
The display
shows "P" when
the parameter
selection knob
is set to ROOM.
A room probe is
connected improp-
erly.
Correct the room probe
connection.
A room probe is
defective.
Refer to "Defective Probes"
The defective
probe pilot light
is on.
A room probe is
defective.
Refer to "defective probes"
9
TC4-2N6F.rev.07
Internal switches
Used to set the operating modes as described in the table below.
#
Parameters
Locked parameters
Unlocked parameters
DESCRIPTION OPERATING MODE
POSITION
SWITCH
ON
OFF
1
° Celsius
° Fahrenheit
Temperature units
ON
OFF
2
3
4
5
6
7
Heater differential
Heater offset
ON
OFF
ON
OFF
1°F (0.6°C)
2 °F (1.1°C)
1°F (0.6°C)
2 °F (1.1°C)