Single Phase units Power to Outdoor Unit
Model Interconnecting Cable
Wires (mm
2
)
Circuit Breaker
(without Heating Element)
Maximum Current
GC24RCC 6 x 2.5 20 A 14.3
GC28RCFA 6 x 2.5 25 A 19.7
GC30RCFA 6 x 2.5 25 A 20.5
Use power supply wire sizes as per local electrical codes and regulations.
Figure 18. Single Phase Units: Electrical Scheme power to outdoor.
1. Outdoor unit
2. Inter- connecting cable
3. Power Supply
4. Semi-automatic switch
5. Indoor unit
6. Quick connector
7. Display control unit
8. Wireless Remote Control
9. Wired Remote Control
(optional)
10. Remote ON/OFF Switch (by
Installer)
11. Control Cable (Shielded)
12. Switch ON/OFF (by Installer)
13. Heater Cable (Optional)
14. Switch ON/OFF for Heater
(by
Installer)
Three Phase units
Model Interconnecting Cable
Wires (mm
2
)
Circuit Breaker
(without Heating Element)
Maximum Current
GC55RCFX 6x2.5 3 x 32 A 27
Use power supply wire sizes as per local electrical codes and regulations
Figure 19. Three Phase Units: Electrical Scheme
GC30RCC 6 x 2.5 25 A 20.4
GC34RCC 6 x 2.5 32 A 24.5
15