CONTROL SYSTEM
Revision 0
12B.4.15 Protection
When all relays meet their function requirements at the same time, there should be an
interval of 0.5 second between every two relays. The action procedures are as follows:
ON state:
AHEAT RV OFAN —> COMP
OFF state:
AHEAT RV OFAN COMP
12B.4.16 Compressor delay protection
At startup if the operation mode is not change, compressor will keep on running during the
first 5 minutes, and it will delay for 3 minutes for a re-start once it was turned off.
Compressor starts at 3 minutes delay unless:
Power is on for the first time or power off lasts for 3 minutes, COMP has no 3 minutes
delay protection;
12B.4.17 RV control
In cooling or drying mode or fan mode, RV is off.
In heating mode, RV will turns on.
Switching between heating mode to other modes, or shutting off in heating mode, RV
delays 2 minutes before turning off.
12B.4.18 Diagnostic
If MCU detect that one of the sensors RT, ICT or, OCT is blow -40ºC or over 85ºC,
the sensor is invalid and will be indicated (see 3.13).But the air-conditioner operates
continuously.
In Cooling or Heating mode, COMP turns on for 20 minutes and turns off for 5 minutes, it is
continuously cycle by cycle. In Dry mode, COMP turns on for 10 minutes and turns off for 6
minutes.
If RT is invalid, system runs at cycle by cycle mode.
If OCT and ICT are invalid, system runs at cycle by cycle mode too.
For cooling only unit’s type, if ICT is wrong, system runs at cycle by cycle mode.