MODELS:
MAA1018A-MAA1060A, MGA1072A
(Single Stage)
MAA2060A-MAA2072A, MGA2072A
(2-Stage)
Installation & Operation Manual
10 & 11 EER Vertical Wall-Mount Air Conditioners
Manufactured By:
A Division of the AIRXCEL
®
Commercial Group
P.O. Box 400 • Cordele, Georgia 31010 • 156 Seedling Drive • Cordele, Georgia 31015
(229) 273-3636 • Fax (229) 273-5154
E-mail: marvairsales@airxcel.com • Internet: www.Marvair.com
The most current version of this manual can be found at www.Marvair.com.
IMPORTANT
This manual may include information for options and features which may not be
included on the unit being installed. Refer to the unit data label or Model Identication
to determine which features and options this unit is equipped with.
INSTALLER: Afx the instructions on the inside of the building adjacent to the thermostat.
END USER: Retain this manual for future reference.
Marvair MAA/MGA Wall Mount AC Installation & Operation Manual
09/2021 Rev.15
Air Conditioner Product Manual
Vertical Wall-Mount Air Conditioners
with Front Control Box Panel

Table of Contents

Questions and Answers

  • A
    Angela WilliamsAug 10, 2025
    Why does my Airxcel Air Conditioner run constantly but not cool enough?
    • K
      Kimberly ScottAug 10, 2025
      If your Airxcel Air Conditioner runs continuously but doesn't cool effectively, first check the air filters and blower operation, removing any airflow restrictions. Then, check for proper refrigerant charge and any possible leaks. Inspect internal components, especially the compressor, for proper operation. If the unit is undersized, consider adding additional units.
  • W
    William FisherAug 15, 2025
    What to do if my Airxcel Marvair MAA1018 Air Conditioner does not run?
    • P
      pnelsonAug 15, 2025
      If your Airxcel Air Conditioner isn't running, start by checking the power supply to ensure it has adequate phase and voltage. Inspect the wiring to the unit and any external breakers or fuses. Also, check the internal circuit protection devices for continuity. Verify the operation of the wall-mounted thermostat. Reset the pressure switch. Finally, check for loose wiring and component failures.
  • K
    kim61Aug 19, 2025
    What to do if Airxcel Air Conditioner blows fuses?
    • M
      mdownsAug 20, 2025
      If your Airxcel Air Conditioner is blowing fuses or tripping the circuit breaker, ensure the circuit ampacity is adequate according to Chapter 2 and correct as necessary. Check the field wiring for errors such as shorts, looseness, or improper connections. Inspect the unit's internal wiring, consulting the wiring and schematic diagrams, and test components (especially the compressor) for shorts. Also, check for excessively high or low supply voltage or phase loss (3ø only), noting voltage range limitations specific to the compressor troubleshooting section.
  • J
    Joshua WagnerAug 25, 2025
    Why does my Airxcel Marvair MAA1018 cycle on high/low pressure?
    • D
      david58Aug 26, 2025
      If your Airxcel Air Conditioner cycles on the high/low pressure limit, examine the blower assembly for proper operation and check for airflow restrictions, such as a dirty air filter. Inspect the blower motor and condenser fan. Look for any blockages or restrictions in the refrigerant circuit, especially the filter drier and capillary tube assembly. If the unit was recently serviced, check for refrigerant overcharge and evacuate/recharge to factory specifications. Finally, check the limit cutout pressures of the pressure control, which should actuate at approximately 60 PSIG (low pressure) and 650 PSIG (high pressure).
  • K
    Kevin MackAug 29, 2025
    How to stop water leak from Airxcel Marvair MAA1018 Air Conditioner?
    • A
      Amy SnyderAug 29, 2025
      If you find water on the floor near your Airxcel Air Conditioner, check the condensate line for any clogs or restrictions. Inspect the condensate pan for obstructions or leaks. Ensure the unit is level.
  • S
    Samantha SmithSep 4, 2025
    Why is there no heating in my Airxcel Air Conditioner?
    • E
      elizabethwalkerSep 4, 2025
      If your Airxcel Air Conditioner (equipped with resistance elements) provides no or reduced heating, check the resistance elements for continuity. Check the continuity across the thermal limit switch. Check the heater contactor relay for proper operation; replace if defective.

Airxcel Marvair MAA1018 Specifications