Marvair MGA3090-3210 Wall Mount AC I&O Manual 03/2021 Rev.6
Part #03836
IMPORTANT
This manual may include information for options and features which may not be
included on the unit being installed. Refer to the unit data label or Model Identication
to determine which features and options this unit is equipped with.
INSTALLER: Afx the instructions on the inside of the building adjacent to the thermostat.
END USER: Retain this manual for future reference.
Manufactured By:
Marvair Division of the AIRXCEL
®
Commercial Group
P.O. Box 400 • Cordele, Georgia 31010 • 156 Seedling Drive • Cordele, Georgia 31015
(229) 273-3636 • Fax (229) 273-5154
www.Marvair.com
The most current version of this manual can be found at www.Marvair.com.
MODELS:
MGA3090A & MGA3120A
(Dual Compressor)
Installation & Operation Manual
10 EER Vertical Wall-Mount Air Conditioners
Installation & Operation Manual
10EER 7.5 & 10 Ton Vertical Wall Mount
Air Conditioners

Table of Contents

Questions and Answers

  • A
    Arthur SmithAug 10, 2025
    Why is there no space heating or reduced heating in my Airxcel Marvair MGA3090A?
    • S
      Scott ByrdAug 10, 2025
      If your Airxcel Air Conditioner (equipped with resistance elements) has no or reduced heating, it could be due to defective heating elements. Check the resistance elements for continuity. It may also be caused by an open thermal limit, so check the continuity across the thermal limit switch. A defective heater contactor could also be the culprit; check the relay for proper operation and replace it if defective.
  • B
    Brandon MooreAug 15, 2025
    Why is my Airxcel Marvair MGA3090A Air Conditioner unit running continuously?
    • D
      Donna JensenAug 15, 2025
      Your Airxcel Air Conditioner might be running for extended periods due to several reasons. It could be a dirty filter or reduced airflow, so check the air filters and blower operation, and remove any airflow restrictions. Another cause might be low refrigerant, in which case you should check for proper charge and possible refrigerant leaks. Component failure, especially of the compressor, could also be the reason. Finally, the unit might be undersized for the job, requiring additional units for greater capacity.
  • U
    umaddenAug 20, 2025
    What to do if my Airxcel Marvair MGA3090A does not run?
    • M
      Mrs. Christina HubbardAug 20, 2025
      If your Airxcel Air Conditioner isn't running, begin by checking the power supply for adequate phase and voltage, and inspect the wiring to the unit, including external breakers or fuses. Also, examine the internal circuit protection devices for continuity. Verify the operation of the wall-mounted thermostat. Reset the pressure switch if the unit is off on a high or low pressure limit. Lastly, check for loose wiring and component failures.
  • T
    tracyriceAug 25, 2025
    Why does my Airxcel Marvair MGA3090A blow fuses?
    • P
      Paige SpencerAug 26, 2025
      If your Airxcel Air Conditioner is blowing fuses or tripping the circuit breaker, it could be due to: 1. Inadequate circuit ampacity. 2. A short, loose, or improper connection in the field wiring. 3. An internal short circuit or loose connection within the unit. 4. Excessively high or low supply voltage or phase loss (3ø only). You should check the field wiring and the unit's wiring for errors. Also, test components for shorts, paying special attention to the compressor. Refer to the electrical requirements and voltage range limitations.
  • E
    Eric SullivanSep 4, 2025
    Why is there water on the floor near my Airxcel Air Conditioner?
    • A
      Amy MurphySep 4, 2025
      If you find water on the floor near your Airxcel Air Conditioner, it could be due to an obstruction in the condensate line, so check for any clogs or restrictions. Another possibility is an obstruction or leak in the condensate pan, so inspect the pan for leaks or blockages. Finally, ensure that the unit is level; if it isn't, level the unit.
  • K
    Kelly WileyDec 1, 2025
    What to do if my Airxcel Marvair MGA3090A Air Conditioner cycles on high/low pressure limit?
    • Y
      yrobbinsDec 1, 2025
      If your Airxcel Air Conditioner is cycling on a high/low pressure limit, it may be caused by several factors: * Loss or restriction of airflow: Inspect the blower assembly for proper operation and check for any airflow restrictions, such as a dirty air filter. Also, inspect the blower motor and condenser fan. * Restriction in the refrigerant circuit: Check for any blockages or restrictions, particularly in the filter drier and capillary tube assembly. * Refrigerant overcharge: If the unit has been recently serviced, it may have been overcharged. In this case, the system should be evacuated and recharged to factory specifications. * Defective pressure control: Verify the limit cutout pressures. The control should actuate at approximately 60 PSIG (low pressure) and 650 PSIG (high pr...

Airxcel Marvair MGA3090A Specifications