73
Rev 2.1
Select Sensor only for DHW demand from selected DHW modulation sensor
Select DHW (S6) Switch for DHW demand from DHW switch (switch replaces the DHW sensor) When sensor
input is shorted burner demand exist outlet sensor will provide the temperature control
Select STAT Terminal for DHW demand from STAT input
Select Auto DHW (S6) or sensor only for DHW demand from DHW switch and DHW sensor
5-3.3 To Change DHW Loop Priority Versus CH Loop
Configure DHW – Domestic Hot Water Configuration DHW Priority vs CH Textbox
(Default: DHW > CH)
Select CH > DHW for no priority over CH loop
Select DHW > CH for priority over CH loop
This parameters determines the priority of DHW vs. the CH call-for heat, when both of these are enabled and active.
(If DHW has a lower priority, it may be boosted to the highest priority temporarily via the DHW Priority Time
parameter.)
5-3.4 To Change DHW Loop Priority Time
Configure DHW – Domestic Hot Water Configuration DHW Override Priority Time Textbox (Default: 5m 0s)
Type in desired time. No limits on this parameter.
If this parameter is non-zero then a DHW demand will take priority over other demand sources for the specified time.
If this persists for longer than this time the priority will expire. The timer is reset when demand from the DHW source
turns off.
5-3.5 To Change DHW Loop Setpoint
Configure DHW – Domestic Hot Water Configuration Setpoint Textbox (Default: 120F)
Type in desired temperature between 32F and 240F (0C and 115C)
This Setpoint is used whenever the time-of-day switch is off or not connected (unused).
5-3.6 To Change DHW Loop Time Of Day Setpoint
Configure DHW – Domestic Hot Water Configuration Time of Day Setpoint Textbox
(Default: 100F)
Type in desired temperature between 32F and 240F (0C and 115C)
This Setpoint is used when the time-of-day switch is on.
5-3.7 To Change DHW Loop Off Hysteresis
Configure DHW – Domestic Hot Water Configuration On Hysteresis Textbox (Default: 7F)
Type in desired temperature between 2F and 30F (1C and 16C)
The on hysteresis is subtracted from the DHW Setpoint to determine the temperature at which DHW demand turns
on.
5-3.8 To Change DHW Loop On Hysteresis
Configure DHW – Domestic Hot Water Configuration Off Hysteresis Textbox (Default: 7F)
Type in desired temperature between 2F and 30F (1C and 16C)
The off hysteresis is added to the DHW Setpoint to determine the temperature at which DHW demand turns off.
5-3.9 To Change The DHW Hysteresis Step Time
Configure DHW – Domestic Hot Water Configuration Hysteresis Step Time Textbox
(Default: 0m0s)
Type in desired time between 0 to 5 minutes
The time needed for one step of hysteresis shift, when the off hysteresis threshold or on hysteresis threshold is shifted
due to a burner-on or burner-off event, respectively. Zero disables this function.