Configure → System Configuration → Temperature Units Textbox (Default: Fahrenheit)
• Select Fahrenheit to show temperature in Fahrenheit
• Select Celsius to show temperature in Celsius
This parameter determines whether temperature is represented in units of Fahrenheit or Celsius degrees.
5-24.7 To Turn On And Off The Unit Using Burner Switch
Operation → Burner Switch Button (Default: Yes/True/On)
This parameter enables or disables the burner control. When it is off, the burner will not fire.
5-24.8 To Enable Pump Test
Diagnostics → Diagnostics Test→ Pump Test Button
Enables the installer to verify that the correct pump contacts are on or off. The Start Test button will test all pump
contacts; pressing an individual pump tests that pump contact only.
5-24.9 To Enable Modulation Test
Diagnostics → Diagnostics Test→ Modulation Test Button
Enables the user to verify that the unit is firing at the correct rate.
5-24.10 To Enable Pilot Test
Diagnostics → Diagnostics Test → Pilot Test Button
Enables the user to verify that the pilot valve is functioning properly. The installer can also perform adjustments for the
pilot flame.