Selection of installation place
The detector is designed for indoor installation only.
The coverage area of one FireProtect 2 (Heat/Smoke) is 50 to 60 m², depending
on the type of premises.
The detector should be installed in every room. The detector is placed in the
center of the ceiling at a distance of 30 cm from light xtures, chandeliers, or
any other decorative objects that may interfere with alarm detection.
If there are beams on the ceiling protruding 30 cm or more, then the detector
must be installed between every two such beams. If the beams protrude by less
than 30 cm, installation on a beam in the central part of the ceiling is allowed.
In halls or narrow corridors, detectors should be installed at a distance of no
more than 7.5 m from each other.
If the ceiling is sloping, the detector is installed at a distance of 60 cm from the
top point of the ceiling. To select an installation place, draw a straight line down
from the top of the ceiling. Then, draw a perpendicular from this line to the
sloping part of the ceiling. The detector is installed at this point.
FireProtect 2 RB (Heat/Smoke) pre-installed battery life is 3.5 years (instead of 7).