Analyze the flue gas and be sure that emission levels of CO, NO
x
, soot, CO
2
or O
2
are according to current regulations.
For reference (current and local regulations has priority)
Note: Emission values shall be according to current and local limitations. In
absence of local limitations refer to current EN 677 for gas firing and current EN
300-2 for oil firing. In correct adjustments can cause damage to people, animals,
nature and also loss of energy.
After running the burner heat the system up to 85 °C and again bleed the air in the
water side. After first heating most of the dissolved air in the system water will be
free for bleeding.
Control all the security and operation devices for proper operation and set values
are according to system needs again.
Call the owner or operator of the boiler house and give the necessary information
for proper operation of the system and warn them about the possible dangers and
limitations and what will they do in case of emergency.