10 | Door Controller
Relay Wiring
Two Form-C contact relays are provided for controlling door
lock mechanisms. The relay contacts are rated at 2A @ 30V
pole (C), a Normally Open pole (NO), and a Normally
Closed pole (NC).
When momentarily delivering power to unlock the locking
hardware (fail secure), the Normally Open and Common
poles are used. When momentarily removing power to
unlock the locking hardware (fail safe), the Normally Closed
and Common poles are used. Check with local building
codes for proper egress door installation.
Door lock mechanisms can generate EMF feedback to the
relay circuit that can cause damage and premature failure
of the relay. For this reason, it is recommended that either
a diode or MOV (metal oxide varistor) be used to protect
the relay.
From the Auxiliary output, the ADC-ACC1-17 can provide
12V DC power for external devices, provided 650 mA is not
power supply is used, it must be UL Listed Class 2 rated. 18
AWG minimum recommended for electric locking hardware.
VO (12 Vdc)
GND
DAT
CLK
1
OSDP PROTOCOL DEVICE
9600 BAUD
ADDRESS 0
1
TB2
VO (12V DC)
GND
LED
BZR
CLK/D1
DAT/D0
TB3
1
BZR
DAT/D0
CLK/D1
LED
SECOND READER PORT
1
TB4
GND
VIN
GND
VO
BZR
1
GND
GND
VIN
VO
DAT/D0
CLK/D1
1
LED
LED
BZR
FIRST READER PORT
1
BZR
VO
DAT/D0
CLK/D1
LED
GND
VIN
GND
TB4
TB3
1
VO (12 Vdc)
CLK
LED
BZR
GND
DAT
TB2
1
REMOTE SERIAL I/O MODULEREMOTE SERIAL I/O MODULE
MR16in
MR16out
FOR EXAMPLE:
MRDT
MR50
MR52
GND
GND
12 Vdc
TR+
TR-
MRDT
FOR EXAMPLE:
MR50
MR16out
MR16in
MR52
GND
TR+
12 Vdc
GND
TR-
OSDP PROTOCOL DEVICE
ADDRESS 1
9600 BAUD
TR+
TR-
FIRST READER PORT
REFER TO THE APPROPRIATE REMOTE SERIAL I/O DEVICE INSTALLATION MANUAL FOR
ADDRESS AND BAUD RATE SETTINGS. DO NOT TERMINATE ANY OF THE DEVICES ON
THE RS-485 MULTI-DROP COMMUNICATION BUS. EACH REMOTE SERIAL I/O DEVICE
MUST BE CONFIGURED WITH AN UNIQUE COMMUNICATION ADDRESS. A MAXIMUM OF
EIGHT REMOTE SERIAL I/O DEVICES MAY BE CONNECTED TO READER PORT 1.
REFER TO THE APPROPRIATE REMOTE SERIAL I/O DEVICE INSTALLATION MANUAL FOR
ADDRESS AND BAUD RATE SETTINGS. DO NOT TERMINATE ANY OF THE DEVICES ON
THE RS-485 MULTI-DROP COMMUNICATION BUS. EACH OSDP DEVICE MUST BE
CONFIGURED WITH AN UNIQUE COMMUNICATION ADDRESS. A MAXIMUM OF TWO OSDP
DEVICES MAY BE CONNECTED TO READER PORT 1.
(12V DC)
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
1
TB2
VO (12 Vdc)
GND
LED
BZR
CLK/D1
DAT/D0
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
NORMALLY CLOSED CONTACT *
DOOR MONITOR SWITCH
REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *
1K,1%
1K,1%
1K,1%
1K,1%
1
VO (12 Vdc)
GND
LED
BZR
CLK/D1
DAT/D0
TB2
1
BZR
DAT/D0
CLK/D1
LED
1
GND
VIN
GND
VO
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
1K,1%
1K,1%
1K,1%
1K,1%
TB3
1
BZR
DAT/D0
CLK/D1
LED
1
TB4
GND
VIN
GND
VO
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
SECOND READER PORT
FIRST READER PORT
FIRST READER PORT
SECOND READER PORT
TB3
TB4
DOOR MONITOR SWITCH
NORMALLY CLOSED CONTACT *
REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *
(DEFAULT) (DEFAULT)
FIRST READER PORT
TB4
TB3
TB2
FIRST READER PORT
GND
GND
12 Vdc
TR+
TR-
GND
TR+
12 Vdc
GND
TR-
TR+
TR-
FIRST READER PORT
1K,1%
1K,1%
1K,1%
1K,1%
Standard Supervised Circuit,
Normally Closed Contact
Standard Supervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Closed Contact
IN2
IN1
TB1
1
}
+
-
DC STRIKE
DIODE
or MOV
TB5
2-C
NC
NC
NO
1
NO
1-C
TO DC POWER
SOURCE
-
+
AC STRIKE
MOV
FUSE
TB5
1
NO
1-C
NC
NC
NO
2-C
AC
TRANSFORMER
TB1 TB2 TB3
1 1 1
12V
PoE
J3
TB5
1
TB4
1
3
4
S1
2
1
ON
S2
7 6 5 4 3 2 1
J7
J1
J4
J5
BT1
K1
J6
K2
TB1
TB5
RESET SWITCH
.15” [3.81 mm] 2.55” [64.77 mm] 2.55” [64.77 mm] .15” [3.81 mm]
.20” [5.08 mm]
5.40” [137.16 mm]
2.35” [59.69 mm]
.20” [5.08 mm]
2.75” [69.85 mm]
TAMPER
SWITCH
CONNECTION
(J7)
ETHERNET
CONNECTOR
(J6)
PoE/12V DC
POWER SELECTOR
JUMPER (J3)
DIP SWITCHES
STATUS LEDs
CHASSIS GND
Ø .125” [Ø3.175 mm]
6 PL
SOLDER SIDE
RELAY K1 LED
RELAY K2 LED
FIELD WIRING
EP1501 WITH INCLUDED
MOUNTING PLATE
TO ETHERNET
NETWORK
OPTIONAL 3-GANG
JUNCTION BOX
OPTIONAL BLANK
COVER W/SCREWS
OPTIONAL MAGNETIC
TAMPER SWITCH
3.85 [97.8]
2.35 [59.7]
5.50 [139.7]
3.63 [92.1]
3.30 [83.8]
3.63 [92.1]
Ø0.16 [Ø4.0]
MR50 MGT HOLES
4PL
Ø0.16 [Ø4.0]
3-GANG MGT HOLES
4PL
Diode Selection:
• Diode current rating: 1x strike current
• Diode breakdown voltage: 4x strike voltage
• For 12V DC or 24V DC strike,
diode 1N4002 (100V/1A) typical
RELAY CIRCUIT WIRING DIAGRAMS
MOV Selection:
• Clamp voltage: 1.5x V AC RMS
• Use UL recognized MOV with appropriate ratings