6 | Door Controller
Bulk Erase Configuration Memory
The bulk erase function can be used for the
following purposes:

database information
Recover from database corruption causing
ADC-ACC1-17 board to continuously reboot
If clearing the memory does not correct the initialization
problem, contact technical support.
BULK ERASE STEPS
Do not remove power during steps 1-8.
1 Set S1 dip switches to: 1 & 2 “ON”, 3 & 4 “OFF”.
2 Press the reset button (S2) next to the DIP switches.
3 
a 0.5 second rate.
4 Within 10 seconds of powering up, change switches
1 and 2 to “OFF.
5 
memory is being erased.
6 Full memory erase takes up to 60 seconds.
7 
8 The ADC-ACC1-17 board will reboot 8 seconds after

this time).