8 Installation
8.2 Electrical Installation
The following must be considered when
installing the electrical system:
Cables must be marked at both ends
according to the illustration.
Screened cables must be used for input
signals from the temperature sensor, flow
switch, and high temperature switch.
Power cables and fuses must be
dimensioned for the installation capacity.
G025211A
The screened cables must be kept well
away from the power cables. The minimum
specified distance is 300 mm.
Screens must be earthed as close as
possible to the earth bar.
Cables to the external alarm panel and for
series computer communication must be
installed according to the manufacturer’s
recommendations.
G003141A
28