7-9
ENGLISH
Registers table
MODBUS protocol manual
$E03C 1 DMD INTEGRATION TIME (in minutes) YES
01 $0001
03 $0003
05 $0005
10 $000A
15 $000F
30 $001E
60 $003C
$E03D 1 BACKLIGHT ON TIME (000÷999 sec.) $0000÷$03E7 NO
$E03F 1 LANGUAGE 0=English NO
1=Deutsch
2=Français
$E0A0 1 COUNTERS RESET 0=none YES
1=reset all energy counters
5=reset hours counter *
$E0A1 1 PEAK RESET 0=none NO
1=reset all peak values
DIGITAL OUTPUT 1
Threshold mode
$E100 5 The register is structured in 5 different parameters and YES
each one corresponds to 1 word.
VARIABLE (see section 7.6) $00XX
MODE 1=threshold with lower limit
2=threshold with upper limit
DELAY in seconds 0=0
1=0.03
2=0.3
3=1
4=3
5=10
6=30
7=100
HYSTERESIS (0÷99%) $0000÷$0063
INTERVENTION VALUE (SET) $0000÷$3A98
(0÷150.00% of FS) (Ex. 100.00% > 10000=$2710)
NOTE: Decimal values are always fixed to 00.
Register Word Description Range/Values Reset