7-10
ENGLISH
Registers table
MODBUS protocol manual
Pulse mode
$E100 5 The register is structured in 5 different parameters and YES
each one corresponds to 1 word.
VARIABLE (see section 7.6) $00XX
MODE 3=pulse (fixed)
PULSE DURATION (150 msec) $0096 (fixed)
PULSE COEFFICIENT (0÷999) $0000÷$03E7
(Ex. 0.125 kWh/imp > 125 = $007D)
PADDING FIELD $0000 (fixed)
$E105 1 PULSE COEFFICIENT (decimal point position) read only NO
0=0.1
1=0.01
2=0.001
$E106 1 PULSE COEFFICIENT (multiplier) read only NO
0=none
1=K
2=M
3=G
4=T
The content of registers $E105 and $E106 depends on the set CT and PT ratios.
DIGITAL OUTPUT 2 (for reading/writing format, see DIGITAL OUTPUT 1)
$E108 5 The register is structured in 5 different parameters which YES
can change according to the mode (threshold or pulse).
$E10D 1 PULSE COEFFICIENT
$E10E 1 PULSE COEFFICIENT
Register Word Description Range/Values Reset

Other manuals for Algodue ELETTRONICA UPM307