PrefaceP–8
Publication 1336 IMPACT-6.2 – March 1998
Table P.F
200 – 240V Drives
Catalog
Number
Maximum
Amp
Rating
Derate
Curve
Heat
Dissipation
Drive
Watts
Heat Sink
Watts
Total Watts
A020
A025
A030
65
78
80
None
210
215
220
933
1110
1110
1143
1325
1330
Table P.G
380 – 480V Drives
Catalog
Number
Maximum
Amp
Rating
Derate
Curve
Heat
Dissipation
Drive
Watts
Heat Sink
Watts
Total Watts
B040
B050
BX040
BX060
65
78
59
78
175
193
175
193
933
1110
933
1110
1108
1303
1108
1303
Table P.H
500 – 600V Drives
Catalog
Number
Maximum
Amp
Rating
Derate
Curve
Heat
Dissipation
Drive
Watts
Heat Sink
Watts
Total Watts
C025
C030
C040
C050
C060
30
35
45
57
62
None
None
None
None
None
141
141
175
193
193
492
526
678
899
981
633
667
853
1092
1174
Amp Rating is at 4kHz. If carrier frequencies above 4kHz are selected, drive Amp Rating must be
derated.
Drive Rating is based on nominal voltage (240, 480, or 600V). If input voltage exceeds Drive
Rating, Drive Output must be derated.
Drive Ambient Temperature Rating is 40_C. If ambient exceeds 40_C, the drive must be derated.
Drive Rating is based on altitudes of 1,000m (3,000 ft) or less. If installed at higher altitude, drive
must be derated.
Refer to the 1336 IMPACT User Manual.
AB Spares