Page 4
40752-165(1)Effective March 2008
Red – ON
White – TRIP
Green – OFF (Reset)
Handle Position Indicator
Color
ON
TRIP
OFF
(Reset)
International
Symbols
ON
OFF
Push-To-Trip
Button
Electro-Mechanical Trip
Device Adjustment Button
(3 Places)
Figure 3-1 MCP Manual Controls
Table 2-1 Terminal Types
①
Terminal Terminal Screw AWG Metric Wire Torque
Cat. No. Material Head Wire Wire Type Value
Body Type Range Range lb-in
(N.m.)
Standard
Terminal
TA250KB Aluminum Socket 4-350 25-185 Cu/AI 275 (31)
MCM
Standard
Terminal
T250KB Stainless Socket 4-350 25-185 Cu 180 (20)
Steel MCM
① Terminal wire connectors are listed for standard wire
sizes as defined in UL486A and UL486B.
Table 3-1 MCP Trip Settings
Cam Motor NEMA Continuous MCP MCP
Setting Full Load Starter Amps Catalog Trip
Current Size Number Setting
Amperes
A 38.5 – 43.4 5 500
B 43.5 – 48.0 5 565
C 48.1 – 53.0 5 625
D 53.1 – 57.6 5 690
E 57.7 – 62.3 5 250 140M-JD8P-C80 750
F 62.4 – 67.3 5 810
G 67.4 – 71.9 5 875
H 72.0 – 76.9 5 935
I 77.0 – 81.6 5 1000
A 57.7 – 64.6 5 750
B 64.7 – 71.9 5 840
C 72.0 – 79.2 5 935
D 79.3 – 86.5 5 1030
E 86.6 – 93.8 5 250
F 93.9 –101.1 5 1220
G 101.2 –108.4 5 1315
H 108.5 –115.3 5 1410
I 115.4 –122.4 5 1500
A 67.4 – 75.3 5 875
B 75.4 – 83.8 5 980
C 83.9 – 92.3 5 1090
D 92.4 –100.7 5 1200
E 100.8 –109.2 5 250
140M-JD8P-D14
F 109.3 –117.6 5 1420
G 117.7 –126.1 5 1530
H 126.2 –134.6 5 1640
I 134.7 –142.8 5 1750
by a color-coded strip for each MCP handle position: red
for ON, white for tripped, and green for OFF. (See Fig.
3-1.)
9
140M-JD8P-D12
1125
1310