Page 4
40752-165(1)Effective March 2008
Red – ON
White – TRIP
Green – OFF (Reset)
Handle Position Indicator
Color
ON
TRIP
OFF
(Reset)
International
Symbols
ON
OFF
Push-To-Trip
Button
Electro-Mechanical Trip
Device Adjustment Button
(3 Places)
Figure 3-1 MCP Manual Controls
Table 2-1 Terminal Types
Terminal Terminal Screw AWG Metric Wire Torque
Cat. No. Material Head Wire Wire Type Value
Body Type Range Range lb-in
(N.m.)
Standard
Terminal
TA250KB Aluminum Socket 4-350 25-185 Cu/AI 275 (31)
MCM
Standard
Terminal
T250KB Stainless Socket 4-350 25-185 Cu 180 (20)
Steel MCM
Terminal wire connectors are listed for standard wire
sizes as defined in UL486A and UL486B.
Table 3-1 MCP Trip Settings
Cam Motor NEMA Continuous MCP MCP
Setting Full Load Starter Amps Catalog Trip
Current Size Number Setting
Amperes
A 38.5 43.4 5 500
B 43.5 48.0 5 565
C 48.1 53.0 5 625
D 53.1 57.6 5 690
E 57.7 62.3 5 250 140M-JD8P-C80 750
F 62.4 67.3 5 810
G 67.4 71.9 5 875
H 72.0 76.9 5 935
I 77.0 81.6 5 1000
A 57.7 64.6 5 750
B 64.7 71.9 5 840
C 72.0 79.2 5 935
D 79.3 86.5 5 1030
E 86.6 93.8 5 250
F 93.9 101.1 5 1220
G 101.2 108.4 5 1315
H 108.5 115.3 5 1410
I 115.4 122.4 5 1500
A 67.4 75.3 5 875
B 75.4 83.8 5 980
C 83.9 92.3 5 1090
D 92.4 100.7 5 1200
E 100.8 109.2 5 250
140M-JD8P-D14
F 109.3 117.6 5 1420
G 117.7 126.1 5 1530
H 126.2 134.6 5 1640
I 134.7 142.8 5 1750
by a color-coded strip for each MCP handle position: red
for ON, white for tripped, and green for OFF. (See Fig.
3-1.)
9
140M-JD8P-D12
1125
1310

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 140M and is the answer not in the manual?

Allen-Bradley 140M Specifications

General IconGeneral
Rated Operational Voltage690V AC
Series140M
Poles3
MountingDIN Rail
Breaking Capacity100kA at 415V AC
Trip Class10, 20
StandardsIEC/EN 60947-2, IEC/EN 60947-4-1

Related product manuals