K-Frame Circuit Breaker
Instruction Leaflet for Alarm Switch and Alarm /Auxiliary Switch Combination
a
WARNING
DO NOT ATTEMPT TO INSTALL OR PERFORM MAIN
-
DEATH, SEVERE PERSONAL INJURY,
OR
SUBSTAN
-
TIAL PROPERTY DAMAGE CAN RESULT FROM CON
-
TENANCE ON EQUIPMENT WHILE IT
IS
ENERGIZED.
TACT WITH ENERGIZED EQUIPMENT. ALWAYS
VERIFY THAT NO VOLTAGE
IS
PRESENT BEFORE
PROCEEDING WITH THE TASK, AND ALWAYS FOL
-
LOW GENERALLY ACCEPTED SAFETY PROCE
-
DURES.
ALLEN-BRADLEY
IS
NOT LIABLE FOR THE MISAP
-
PLICATION OR MISINSTALLATION
OF
ITS PROD
-
UCTS.
The user is cautioned
to
observe all recommendations,
warnings, and cautions relating to the safety of personnel
and equipment as well as all general and local health and
safety laws, codes, and procedures.
The recommendations and information contained herein
are based on Allen-Bradley experience and judgement,
but should not be considered to be all
-
inclusive or cover
-
ing every application or circumstance which may arise. If
any questions arise, contact Allen-Bradley for further
information or instructions.
1.
INTRODUCTION
General Information
The alarm (signal)/lockout switch
(ASL
switch) is
attached to a plug
-
in module available in the following
combinations (see Fig.
1-1):
One or two ASL switches
One auxiliary switch and one ASL switch
The plug
-
in module is mounted in slots in the top of the
trip unit and occupies the accessory mounting cavity in
the circuit breaker frame.
The
ASL
switch provides remote signaling and interlock
-
ing when the circuit breaker trips; it consists of one or two
single
-
pole, double
-
throw (SPDT) switches. Each SPDT
Fig.
I
-
1.
Alarm (Signal)/iockout
Switch
Installed in
K
-
Frame Circuit Breaker
switch has a make (alarm) and a break (lockout) contact;
it is mounted so that the switch actuator arm is controlled
by the circuit breaker operating mechanism cradle. The
actuator arm extends past the operating mechanism cra
-
dle; therefore, only one plug
-
in module containing an
ASL
switch or switches can be used in a circuit breaker.
When the circuit breaker is in the
ON
or
OFF
position, the
cradle holds the make contact open and the break con
-
tact closed. When the circuit breaker is in the tripped
position, the make contact is closed and the break con
-
tact is open. Any type
of
trip operation (for example, auto
-
matic trip, shunt trip, or undervoltage release) actuates
the
ASL
switch.
The auxiliary switch in the combination accessory indi
-
cates circuit breaker contacts status and is used for
remote signaling and system interlocking purposes. Each
SPDT switch has one “a” and one
“b” contact. The plug
-
in
module mounts in the accessory mounting cavity of the
circuit breaker
so
that the switch actuator arm rests
against the molded crossbar. When the molded crossbar
is in the contacts
-
closed position, the “a” contact of each
SPDT switch is closed and the
“b” contact is open. When
40752-035(1)
Effective 3/02
Bul. 140U
Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 140U and is the answer not in the manual?

Allen-Bradley 140U Specifications

General IconGeneral
BrandAllen-Bradley
Model140U
CategoryCircuit breakers
LanguageEnglish

Summary

K-Frame Circuit Breaker

Introduction to ASL Switch

Provides general information about the Alarm (Signal)/Lockout (ASL) switch and its function.

Installation Procedures

Details on how to field-install ASL switches and accessory combinations in K-Frame circuit breakers.

General Installation Steps

General Installation Steps

Step-by-step instructions for preparing and installing the accessory in the circuit breaker.

Alarm (Signal)/Lockout Switch Installation

Specific steps for inserting the ASL switch module into the trip unit.

Accessory Combination Installation

Steps for installing the accessory combination switch module.

Circuit Breaker Cover Installation

Instructions for installing the circuit breaker cover after accessory installation.

Testing the ASL Switch

Procedures to test the ASL switch using a continuity tester or ohmmeter.

Testing the Auxiliary Switch

Procedures to test the auxiliary switch using a continuity tester or ohmmeter.

Final Installation and Connection

Steps for installing the circuit breaker and connecting accessory leads.