POINT I/O 24V DC Expansion Power Supply 15
Publication 1734-IN058C-EN-P - October 2015
Current Derating for Mounting
ESD immunity IEC6100-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from 30…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100%AM @ 1890 MHz
EFT/B immunity IEC 61000-4-4:
±4 kV @ 5 kHz on power ports
Surge transient immunity IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
Conducted RF immunity IEC61000-4-6
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Environmental Specifications
Attribute Value
1.3
1.0
0.5
Horizontal – 1A @ (10…19.2V); 1.3A @ (19.2…28.8)
Vertical – 1A @ (10…28.8V)
10 19.2 28.8
Voltage
Current
43971