EasyManua.ls Logo

Allen-Bradley 1785 PLC-5 - Page 25

Allen-Bradley 1785 PLC-5
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addressing Reference
1785 PLC-5
22
T
able P
Example
PID Control Addresses
To Address: PLC Data Type: Example Address:
Whole PD Control Structure structure $PD13:0
Set-point value IEEE float $PD13:0.SP
Proportional-gain value IEEE float $PD13:0.KP
PID-initialized bit bit $PD13:0.INI
SP out-of-range bit bit $PD13:0.SPOR
T
able Q
PID
Control Block in Integer File
Word: Contains: Term: Range:
0 Bit 15 Enabled (EN)
Bit 13 Done (DN)
Bit 11 Set point out of range
Bit 10 Output alarm, lower limit
Bit 9 Output alarm, upper limit
Bit 8 DB, set when error is in DB
Bit 7 Resume last state (0 = yes, 1 = hold last state)
Bit 6 Derivative action (0 = PV, 1 = error)
Bit 5 Setpoint descaling (0 = no, 1 = yes)
Bit 4 Set output (0 = no, 1 = yes)
Bit 3 Output limiting ((0 = no, 1 = yes)
Bit 2 Control (0 = direct, 1 = reverse)
Bit 1 Mode (0 = automatic, 1 = manual)
Bit 0 Equation (0 = independent, 1 = ISA)
1 reserved
2 Setpoint SP 0 thru 4095 (unscaled)
S
min
thru S
max
(scaled)
3
Independent: Proportional gain (unitless) K
P
0 thru 327.67
3
ISA: Controller gain (unitless) K
C
0 thru 327.67
4
Independent: Integral gain (1/s) K
I
0 thru 327.67
ISA: Reset term (minutes per repeat) T
I
0 thru 327.67
5
Independent: Derivative gain K
D
0 thru 327.67
ISA: Rate term x 100 (minutes) T
D
0 thru 327.67
6 Feedforward or bias FF/Bias 0 thru 4095
7 Maximum scaling S
max
–32,768 thru +32,767
8 Minimum scaling S
min
–32,768 thru +32,767
9 Dead band DB 0 thru 4095 (unscaled)
S
min
thru S
max
(scaled)
10 Set output SETOUT 0 thru 100%
11 Maximum output limit (% of output) L
max
0 thru 100%
12 Minimum output limit (% of output) L
min
0 thru 100%
13 Loop update time (seconds) dt 0.01 thru 327.67

Related product manuals