22 FLEX I/O AC Digital Output Modules
Publication 1794-IN103D-EN-P - July 2018
Derating Curve for 1794-OA16
Mounting Temperature, max.
Normal horizontal 55 °C
Other mounting positions (including inverted horizontal, vertical) 51 °C
0
72
10 20 30 40 50 55 60
V
in
On-state
V
oltage
(V AC)
Ambient Temperature
o
C
The area within the curve represents the safe operating range for the module under
various conditions of user supplied 120V AC supply voltages and ambient temperatures.
= Other mounting positions (including inverted horizontal, vertical)
safe operating range
80
88
96
102
110
115
120
132
51
= Normal mounting safe operating range. Includes
130