Process Control Instructions 
 
108  Rockwell Automation Publication 1756-RM006K-EN-P - November 2018 
SPPercent is invalid 
The CloseOut is pulsed whenever SP < Position feedback. When this occurs, the 
instruction sets OpenTime = 0 and the duration for which CloseOut is to be 
turned on is calculated as: 
 
If CloseTimen-1 < CycleTime, then add Deadtime to CloseTime. 
If CloseTime > MaxOnTime, then limit to MaxOnTime. 
If CloseTime < MinOnTime, then set CloseTime to 0. 
If any of the following conditions exist, CloseOut will not be pulsed and 
CloseTime will be cleared to 0.0. 
ClosedFB is true or PositionPercent    0 
CycleTime = 0 
CloseRate = 0 
SPPercent is invalid 
OpenOut and CloseOut will not be pulsed if SPPercent equals PositionPercent. 
Both OpenTime and CloseTime will be cleared to false. 
Affects Math Status Flags 
No 
Major/Minor Faults 
None specific to this instruction. See Common Attributes for operand-related 
faults.