Process Control Instructions 
 
238  Rockwell Automation Publication 1756-RM006K-EN-P - November 2018 
Output 
Parameters 
Data 
Type 
Description  Values 
CV3HandFBInv  BOOL  CV3 HandFB < 0 or > 100. Limit value used for CV3.  Bit 8 of Status3CV3 
CV1PV1ModelGain
Inv 
BOOL  CV1PV1ModelGain is 1.#QNAN or -1.#IND. (Not A 
Number), or ± 1.$ ( Infinity ∞ ). 
Bit 9 of Status3CV1 
CV2PV1ModelGain
Inv 
BOOL  Entered value for CV2 - PV1 Model Gain is 1.#QNAN 
or -1.#IND. (Not A Number), or ± 1.$ ( Infinity ∞ ). 
Bit 9 of Status3CV2 
CV3PV1ModelGain
Inv 
BOOL  Entered value for CV3 - PV1 Model Gain is 1.#QNAN 
or -1.#IND. (Not A Number), or ± 1.$ 
(Infinity ∞). 
Bit 9 of Status3CV3 
CV1PV2ModelGain
Inv 
BOOL  CV1PV2ModelGain is 1.#QNAN or -1.#IND. (Not A 
Number), or ± 1.$ ( Infinity ∞ ). 
Bit 10 of Status3CV1 
CV2PV2ModelGain
Inv 
BOOL  Entered value for CV2 - PV2 Model Gain is 1.#QNAN 
or -1.#IND. (Not A Number), or ± 1.$ ( Infinity ∞ ). 
Bit 10 of Status3CV2 
CV3PV2ModelGain
Inv 
BOOL  Entered value for CV3 - PV2 Model Gain is 1.#QNAN 
or -1.#IND. (Not A Number), or ± 1.$ 
(Infinity ∞). 
Bit 10 of Status3CV3 
CV1PV1ModelTCIn
v 
BOOL  Entered value for CV1 - PV1 Model Time Constant < 
0. 
Bit 11 of Status3CV1 
CV2PV1ModelTCIn
v 
BOOL  Entered value for CV2 - PV1 Model Time Constant < 
0. 
Bit 11 of Status3CV2 
CV3PV1ModelTCIn
v 
BOOL  Entered value for CV3 - PV1 Model Time Constant < 
0. 
Bit 11 of Status3CV3 
CV1PV2ModelTCIn
v 
BOOL  Entered value for CV1 - PV2 Model Time Constant < 
0. 
Bit 12 of Status3CV1 
CV2PV2ModelTCIn
v 
BOOL  Entered value for CV2 - PV2 Model Time Constant < 
0. 
Bit 12 of Status3CV2 
CV3PV2ModelTCIn
v 
BOOL  Entered value for CV3 - PV2 Model Time Constant < 
0. 
Bit 12 of Status3CV3 
CV1PV1ModelDTIn
v 
BOOL  Entered value for CV1-PV1 Model Deadtime < 0.  Bit 13 of Status3CV1 
CV2PV1ModelDTIn
v 
BOOL  Entered value for CV2-PV1 Model Deadtime < 0.  Bit 13 of Status3CV2 
CV3PV1ModelDTIn
v 
BOOL  Entered value for CV3 - PV1 Model Deadtime < 0.  Bit 13 of Status3CV3 
CV1PV2ModelDTIn
v 
BOOL  Entered value for CV1-PV2 Model Deadtime < 0.  Bit 14 of Status3CV1 
CV2PV2ModelDTIn
v 
BOOL  Entered value for CV2-PV2 Model Deadtime < 0.  Bit 14 of Status3CV2 
CV3PV2ModelDTIn
v 
BOOL  Entered value for CV3 - PV2 Model Deadtime < 0.  Bit 14 of Status3CV3 
CV1PV1RespTCInv  BOOL  Entered value for CV1-PV1 Response Time Constant 
< 0. 
Bit 15 of Status3CV1 
CV2PV1RespTCInv  BOOL  Entered value for CV2-PV1 Response Time Constant 
< 0. 
Bit 15 of Status3CV2 
CV3PV1RespTCInv  BOOL  Entered value for CV3 - PV1 Response Time 
Constant < 0. 
Bit 15 of Status3CV3 
CV1PV2RespTCInv  BOOL  Entered value for CV1-PV2 Response Time Constant 
< 0. 
Bit 16 of Status3CV1