Rockwell Automation Publication 1756-RM006K-EN-P - November 2018  343 
TimingMode  DINT  Selects timing execution mode. 
0 = Periodic mode 
1 = Oversample mode 
2 = Real time sampling mode 
Valid = 0 to 2 
Default = 0 
RTSTimeStamp  DINT  Module time stamp value for real time sampling mode. 
Valid = 0 to 32,767ms 
Default = 0 
 
Output Parameter  Data Type  Description 
EnableOut  BOOL  Indicates if instruction is enabled. 
Cleared to false if Out overflows. 
Out  REAL  The calculated output of the 
algorithm. 
DeltaT  REAL  Elapsed time between updates. 
This is the elapsed time in seconds 
used by the control algorithm to 
calculate the process output. 
Status  DINT  Status of the function block. 
InstructFault (Status.0)  BOOL  The instruction detected one of the 
following execution errors. This is 
not a minor or major controller 
error. Check the remaining status 
bits to determine what occurred. 
WLeadInv (Status.1)  BOOL  WLead < minimum value or 
WLead > maximum value. 
WLagInv (Status.2)  BOOL  WLag < minimum value or WLag 
> maximum value. 
ZetaLeadInv (Status.3)  BOOL  Lead damping factor < minimum 
value or lead damping factor > 
maximum value. 
ZetaLagInv (Status.4)  BOOL  Lag damping factor < minimum 
value or lag damping factor > 
maximum value. 
OrderInv (Status.5)  BOOL  Invalid Order value. 
WLagRatioInv (Status.6)  BOOL  WLag:WLead ratio greater than 
maximum value. 
TimingModeInv (Status.27)  BOOL  Invalid TimingMode value. 
For more information about timing 
modes, see Function Block 
Attributes. 
RTSMissed (Status.28)  BOOL  Only used in real time sampling 
mode. Set when 
ABS (DeltaT - RTSTime) > 1 
millisecond. 
RTSTimeInv (Status.29)  BOOL  Invalid RTSTime value. 
RTSTimeStampInv (Status.30)  BOOL  Invalid RTSTimeStamp value. 
DeltaTInv (Status.31)  BOOL  Invalid DeltaT value.