Rockwell Automation Publication 1794-IN082D-EN-P - January 2019 19
FLEX I/O EtherNet/IP Adapters
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHZ sine-wave 80% AM from 2000…2700MHz
EFT/B immunity
IEC 61000-4-4:
±4 kV at 5 kHz on power ports
±2 kV at 5 kHz on communication ports
Surge transient immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±2 kV line-earth (CM) on communication ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications
Certifications (when product is
marked)
(1)
Value
c-UL-us
• UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E65584.
• UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S.
and Canada. See UL File E194810.
CE
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
RCM
Australian Radiocommunications Act, compliant with:
• EN 61000-6-4; Industrial Emissions
Environmental Specifications
Attribute Value