Rockwell Automation Publication 7000-TG002J-EN-P - March 2015 21
Fault Messages Chapter 1
X External 1…16 1…16 These are the optional additional external faults available
when there is an additional XIO board installed. This is
configured with XIO Ext Faults (P593), and this message will
appear if the specific input (1-16) is configured in Fault Config
as a Class 1 or Class 2 fault.
Review XIO board drawing:
Identify source of input from the external fault XIO board print and investigate the cause of
the fault.
Verify voltage signals from external sources.
XExt Cooling Loss
(C-Frame only)
65 The drive has detected the loss of the ability to provide
cooling for the drive. This is detected through feedback from
the heat exchanger cooling fans contactors and overloads.
Review the inputs to the drive liquid cooling XIO and determine the source of the missing
signals.
Investigate the heat exchanger fans and control for a cause.
Check the liquid cool XIO card.
X Fault Code 159 159 Line voltage and/or line frequency loss at the drive input.
This fault is active when the drive operates in HPTC mode.
This fault is valid for firmware 10.002 and later revisions.
Bit 15 of Par#281 ('Drive Fault3') will be set for the fault.
Investigate power disturbances at the drive input.
Investigate if the fault is caused by starting or stopping the across the line starter or soft
starter.
Verify voltage sensing board VSB1 is free of visible damage. Use a multimeter to check
resistances against nameplate ratings.
Verify the parameter setting for line loss: Par #698 ('Line Loss Trip') is more or less than the
default value
Upload black box data from the drive and contact MV Tech Support
X Fault Code 648 648 Rectifier A3 Fault: A3 diagnostic test failure on the OIBBS Cycle the control power
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare part
replacement
X Fault Code 649 649 Rectifier A4 Fault: A4 diagnostic test failure on the OIBBS Cycle the control power
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare part
replacement
X Fault Code 650 650 Rectifier A5 Fault: A5 diagnostic test failure on the OIBBS Cycle the control power
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare part
replacement
X Fault Code 680 680 Inverter A3 Fault: A3 diagnostic test failure on the OIBBS Cycle the control power
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare part
replacement
X Fault Code 681 681 Inverter A4 Fault: A4 diagnostic test failure on the OIBBS Cycle the control power
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare part
replacement
X Fault Code 682 682 Inverter A5 Fault: A5 diagnostic test failure on the OIBBS Cycle the control power
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare part
replacement
All Drive Types
PF7000A
PF7000B
PF7000C
Marine Drive
Heat pipe Drive
Fault Message Fault Code Description Recommended Action(s)