24 Rockwell Automation Publication 7000-TG002J-EN-P - March 2015
Chapter 1 Fault Messages
X X X InvHSnk OvrTemp 178 The temperature detection on the inverter heatsink,
connected to Channel A fiber-optic receiver RX7 on FOI-M-A,
has exceeded InvHSink TempTrp (P315).
Confirm actual temperature in parameters is not higher than the trip value – If so,
investigate the conditions of the drive (ambient/ loading/ elevation / ventilation/ filter
status /heatsink clogging).
Check the sensor and temperature offline (ambient) for accuracy.
Check for any harmonic and capture DC current waveforms on ACB board.
Ensure that the fan is working properly and that the air flow is sufficient in this cabinet.
X X X InvHSnk Sensor 181 While Not Running, The drive has detected a missing
temperature sensor connected to the TFB on the inverter
heatsink. A missing sensor can result in either a Fiber Optic
Loss fault or a Sensor fault because a missing sensor can be
interpreted as either 0 °C or over 100 °C, and both are
unrealistic values.
Verify sensor is completely seated properly on TFB.
Measure sensor resistance.
Replace if necessary.
X Inv OIBB Com Flt 628 Inverter OIBBS communication fault
: Communication failed to
the OIBBS. Communication from the inverter OIBBS is lost.
Verify the drive settings. If the drive does not use the STO feature, disable STO and verify
that the correct OIBB type is installed.
Verify the inverter Optical Interface Base Board Safety (OIBBS) connections to the DPM.
Check and cycle the control power to the safety system (OIBBS).
If the same fault trips the drive again, contact the manufacturer for the OIBBS spare part
for replacement.
X InvOvrVoltage SW 468 The drive has detected an over-voltage at the inverter output
terminals in software for long cable applications. A fault is
issued if the drive is gating else a warning is issued.
Verify that the Motor Over Voltage Trip (P181) is set correctly.
Verify that the motor cables are not disconnected.
Contact MV Tech Support for assistance.