38 Rockwell Automation Publication 7000-TG002J-EN-P - March 2015
Chapter 1 Fault Messages
X Rec PS Out Rng 634 Rectifier power supply out of range: The rectifier OIBBS
diagnostic subsystem has detected an out of range power
supply voltage on the internally generated supplies.
Verify the STO system power supply/connection to the OIBBS.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for spare parts of the power
supply and/or OIBBS for replacement.
X Rec PSD Fault 658 Rectifier power structure diagnostic fault: The safety control
system has detected a fault in one or more SGCTs. Incorrect
SGCT unit feedback was detected.
Resolve all other faults first
Ensure there are OIB2s are installed in the OIBBS, not the OIBs
Ensure proper configuration setting of the SPS with drive hardware
Check the LV wiring from the input device feedback
Check the LV wiring/connectors to the OIBBS and ACB.
Verify correct STO configuration settings
Shut off all the power to the drive. Test the SGCTs according to the procedures in the User
Manual.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare part(s)
for replacement.
X Rec S1 Stuck 640 Rectifier S1 stuck
: The rectifier OIBBS diagnostic subsystem
has detected a fault.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare parts for
replacement.
X Rec S2 Stuck 641 Rectifier S2 stuck: The rectifier OIBBS diagnostic subsystem
has detected a fault.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare parts for
replacement.
X Rec S3 Timeout 644 Rectifier S3 timeout: The rectifier OIBBS diagnostic subsystem
has detected a fault. A problem of timing function on the
OIBBS has been detected.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare parts for
replacement.
X RecSTOInp Invld 643 Rectifier safety input invalid
: The rectifier OIBBS diagnostic
subsystem has detected an invalid control input state.
Verify the wiring of the rectifier OIBBS.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare parts for
replacement.
X Rec Temp Out Rng 635 Rectifier temperature out of range: The rectifier OIBBS
diagnostic subsystem has detected an out of range
temperature.
Verify the airflow in the low voltage control compartment.
Shut off the control power to let temperature drop off.
Cycle the control power.
If the same fault still trips the drive, contact the manufacturer for the OIBBS spare parts for
replacement.
X Rec WtchDg T Out 633 Rectifier watchdog timeout: A failure of the rectifier OIBBS
diagnostic subsystem was detected.
Verify all the connections for OIBBS, OIB2 on rectifier side.
This fault will only reset upon cycling control power.
Cycle the control power, and if the same fault still trips the drive, contact the manufacturer
for spare parts of the OIBBS, OIB2 and/or the connections for replacement.